Star Delta Air Break Motor Starter

MOQ : 10 Piece

Business Type Manufacturer, Exporter, Supplier
Voltage 360V, 440V
Frequency 50Hz, 60Hz

Preferred Buyer From

Location Worldwide

Quality Features for Convenient Operation
Paragon PE-1 Star-delta Starters are Available in Two Designs:fully Automatic and Semi-automatic.
 
Fully Automatic
The Motor Starts in ‘star’ When the Green Start Button is Pressed. Change Over to ‘delta’ is Automatic. Controlled By An Adjustable Thermal Timer Incorporated in the Starter.
 
Semi Automatic
The Motor Starts in ‘star’ When the Start Button is Pressed. this Button Must Be Released Only After the Motor Picks Up Speed. On Releasing It. Contractors Change Over to ‘delta’
 
Construction Features and Performance in the Two Designs are Identical.
 
Construction
Paragon PE-1 Star-delta Starters have Three Pe-1 Contractors and One Triple Pole Bimetallic Thermal Overload Relay Suitably Wired and Interconnected.
 
Contact System
The Contactor Consists of a Fixed Contact System with a Magnetic Core and Solenoid Coil. and a Moving Contact System with Armature. These Air Break Contractors are of Bounce Free Double Break Design with Sliver Contact Tips. Springs Used are of Stainless Steel and Contacts are Tested for Millions of Operations.
 
Overload Protection
The Triple Pole Bimetallic Thermal Overload Relay is of the Hand Reset Type. It Unmistakably Indicates Overload. a Temperature Compensation Device Prevents the Relay from Being Affected By Variation in Ambient Temperature. Housed in a Bakelite Enclosure the Entire Relay Unit is Accurately Calibrated and Individually Tested On An Automatic Test Bench .setting Can Be Adjusted By Means of a Pointer. Relays are Available in Different Ranges to Suit Motors Up to 25HP
 
Under voltage Protection
Under Voltage Protection is Provided By the Coil of the Contactor. Machine Wound. Vacuum Impregnated and Baked. PE-1 Coils are Tested for Inter- Turn short Circuit. They Undergo a 4000 V Impulse Test.
 
Push Button
Shrouded Start and Stop Push Buttons are Mounted On the Front Cover. the Stop Button Which Can Be Latched in the Pressed Position from Outside also Acts as the Reset Button for Hand Reset of the Overload Relay.

Yes! I am interested

  • Additional Images

  • OIL IMMERSED STARDELTA MOTOR STARTER

  • PE-1 STAR DELTA MOTOR STARTER

  • PEHD STAR DELTA MOTOR STARTER

  • PU-2 DOL STARDELTA MOTOR STARTER

Looking for "Star Delta Air Break Motor Starter" ?

Piece

Explore More Products


Close

Raise your Query

Hi! Simply click below and type your query.

Our experts will reply you very soon.

WhatsApp Us